Operating Instructions PCI SC22-3 Safety Controller
44 135369 06.03.08 INSTRUCTION MANUAL - EUROPEAN VERSION
5.1.6.4 Adding Two-Hand Control
1) From Add Safety Input menu (screen 8 on page 41) click on an
appropriate icon and click OK (or double-click on
the icon). Screen 17 on page 44 is shown.
If the default settings are NOT to be used, proceed as follows:
2) Add Name: e.g. THC01.
3) Select appropriate Circuit Type: 2X Complementary, PNP
switch.
4) From drop down menu(s), select Input terminals: e.g. S7, S8, S9
and S10.
5) Set Mapped to: e.g. SO3.
6) If the default settings are NOT to be used, click on:
Advanced Settings
Set Closed-open debounce time:
Set Open-closed debounce time:
7) On completion click OK to exit.
The Reset Logic is set to Automatic for Two-Hand Control devic-
es. There are no other reset options.
5.1.6.5 Adding Muting Sensor Pair
1) From Add Safety Input menu (screen 8 on page 41) click on an
appropriate icon and click OK (or double-click on the
icon). Screen 18 on page 44 is shown.
If the default settings are NOT to be used, proceed as follows:
2) Add Name: e.g. M1+M2.
3) Select appropriate Circuit Type: Dual channel, 4 terminal.
4) From drop down menu(s), select Input terminals: e.g. S13, S14,
S15 and S16.
5) Set Mapped to: e.g. OS01.
6) If the default settings are NOT to be used, click on:
Advanced Settings
Set Closed-open debounce time:
Set Open-closed debounce time:
7) On completion click OK to exit.
Screen 17 Screen 18