DIP Switch Configurable Gateway for the M-GAGE™ NodeFeaturesIP67 Base2.4 GHzIP20 Base900 MHzThe SureCross™ wireless system is a radio frequency networ
UL ListingMaximum ambient temperature: 70°CMounting instructions: See document 132607Power rating: 10 to 30V dc, UL Class 2Enclosure environmental rat
Exporting SureCross RadiosIt is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers w
The SureCross DX80 Wireless NetworkThe SureCross DX80 wireless I/O network provides reliable monitoring without the burden of wiring or conduit instal
Wiring DiagramsM-GAGE™ Gateway I/O MappingI/O Terminal Label M-GAGE Gateway M-GAGE Node I/O1 DI1 Discrete IN 1 to Device 1, Baseline 142 DI2 Discrete
Terminal Block (IP67 Base)PWRGNDDO6DO5DO4DO3DO2DO1PWRGNDDI6DI5DI4DI3DI2DI1DIx. Discrete IN x.DOx. Discrete OUT x.GND. Ground/dc common connection.PWR.
DIxPWR or SPxSureCross DeviceDIxGNDSureCross DeviceWiring Diagrams for Discrete OutputsConnecting dc power to the communication pins will cause perman
I/OPointModbus Holding Register I/O Type Units I/O Range Holding RegisterRepresentationTerminalBlock La-belsGateway Any Node Min.ValueMax.ValueMin.(De
SwitchesDevice Settings 1 2 3 4 5 6 7 8Node 1 baseline filter ON ONNode 1: threshold = 100, hysteresis = 30 OFF* OFF*Node 1: threshold = 150, hysteres
Verify CommunicationsAfter powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. Verify LED 1 is green. Un
Consumption: Less than 1.4 W (60 mA) at 24V dcHousingPolycarbonateWeight: 0.26 kg (0.57 lbs)Mounting: #10 or M5 (M5 hardware included)Max. Tightening