Banner Q45 Series User Manual

Browse online or download User Manual for Sensors Banner Q45 Series. Banner Q45 Series User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Banner model 45SD plug-in bus cards enable a Banner Q45X Series sensor to
establish a logical relationship between the sensor's output and other compat-
ible devices on an SDS
bus network. 45SD cards are part of a family of bus
expansion cards for Q45X sensors which includes models for use on AS-
Interface, DeviceNet
, Seriplex
®
, and other data buses.
Use of a 45SD bus expansion card turns the Q45X into a "smart" sensor which
can be connected to an SDS bus network using a simple "dumb drop" junction
box or a "T" connector. Plugging a bus expansion card into a Q45X Series
sensor automatically converts the basic sensor outputs to a pair of datacom
connections with the proper protocol for use on an SDS
bus network. Q45X
sensors without bus cards (i. e. "dumb sensors") may also be added to any bus
system, via a "smart drop" junction box. Basic Q45X sensors (without bus
expansion cards) interface directly to PLC dc inputs. See the functional
schematics on the other side of
this data sheet. The block dia-
gram at the right illustrates how
"smart" and "dumb" Q45X Series
sensors can be mixed together on
the same bus network.
On a Q45X Series sensor with a
45SD1 expansion card installed, a
green LED lights to indicate
POWER ON, and a red LED indi-
cates received light signal strength
by means of Banner's patented
AID
system (see below).
NOTE: The yellow sensor LED is
disabled when a bus network card is installed.
Emitter model Q45X6EQ has green indicator only.
SDS™ is a trademark of Honeywell Micro Switch Division
Printed in USA P/N 39669D6B
For use with Q45X Series Photoelectric Sensors on SDS
Bus Networks
45SD Series Bus Expansion Cards
Data
Input
Input
Input
PLC
Q45X
Q45X
Q45X
Q45XQ45XQ45XQ45XQ45X
Q45X Q45X Q45X Q45X
"Dumb" Sensors
(x4)
"Smart" Sensors
(x4)
Smart
Drop
Dumb
Drop
"T"
"Dumb" Sensors
(x3)
"Smart" sensor
Connector
Bus
Specifications, Q45X Series Sensors using 45SD Expansion
Card (see Q45X data sheet, p/n 37735, for further information).
Supply voltage and current:
The sensor is powered by the bus network (11 to 25V dc; 60
mA combined current for Q45X sensor and 45SD card).
Output configuration: Standard CAN transceiver, non-isolated.
Conforms to SDS
protocol.
Circuitry protection: Protected in the event of reverse power
supply polarity and loss of ground (neither condition will harm
the sensor or interrupt other communications on the network).
Sensor response time: 2 milliseconds. The total response time
is the sum of the sensor response time and the network response
time.
Status indicators (visible through transparent sensor top cover):
A green LED lights to indicate POWER ON; a red Banner AID
System (
U.S. patent no. 4356393) LED lights when the sensor is
seeing it's modulated light source, and pulses at a rate proportional
to the strength of the received light signal. Emitter model Q45X6EQ
has green indicator only.
Cable: Sensors require SDS
5-pin mini-style quick discon-
nect cable, available from Turck, Lumberg, or Brad Harrison
(see page 2).
Operating temperature range: -10 to +70°C (14 to +158°F)
Relative humidity: 0 to 95%, non-condensing
Model Part No. Used with Sensor Communication
45SD1 40060 All Q45XB6 models, SDS level 4 binary input 1.1.1.5
except emitter
45SDE1 40908 Q45X6EQ emitter Allows emitters to be powered from the bus;
not communicate
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Bus Expansion Cards

Banner model 45SD plug-in bus cards enable a Banner Q45X Series sensor toestablish a logical relationship between the sensor's output and other c

Page 2 - 45SD Bus Expansion Cards

Q45X sensor hookup, 45SD expansion card installed(Q45X base, male connector):RemovalModules are removed through the top of the sensor. The procedure

Page 3 - ATTRIBUTES

SDS Model Specification for 45SD1 Bus CardThe 45SD card conforms to the following SDS model: Level 4 Binary Input, 1.1.1.5ATTRIBUTESAttribute Descript

Page 4

9 Bus Diagnostics Register: This is a 2 byte read only register. When an error occurs, the corresponding bit is set.Byte 1bit 0 ROM Checksum Errorbi

Page 5

61 Configuration Register:This is a single byte, 8 flags.bit 0 - 2 not used.bit 3 Disable re-transmission of COS messages R/W . When this bit is set

Page 6

0 Diagnostic Event Counter: This event is sent when ever a flag in attribute 9 is set. This event also sends one databyte. This byte contains the v